During VFD commissioning, excessive motor vibration and noise is observed at certain speeds. This is most likely caused by:
  • Insufficient motor cooling fan speed
  • Mechanical resonance coinciding with VFD output frequency at that speed✔️
  • Incorrect V/Hz ratio setting
  • DC bus overvoltage due to regeneration
Correct Answer Explanation
Mechanical resonance occurs when the VFD output frequency excites the natural resonant frequency of the motor-load mechanical system (shaft, bearings, coupled machine). This can cause excessive vibration, noise, and fatigue failure. The solution is to program skip frequencies (forbidden speed ranges) in the VFD to avoid continuous operation at resonant frequencies.